CASE HISTORY 195

 

UNSTABLE REBOILER HP STEAM FLOW

 

A high pressure steam flow control in a reboiler on a column in a petro-chemical refinery continually cycled when placed in automatic.  Several attempts had been made to tune the controller, but these had been unsuccessful.  The operators had to control the flow manually but had great difficulty in getting it to the desired flow value.  Some open and closed loop tests were performed on the flow which revealed some remarkable things:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 1

 

Figure 1 is a test with controller firstly being set in automatic (closed loop testing), with the “as-found” tuning parameters in the controller, and a few small SP (set point) steps being made.  Once that was done the controller was placed in manual (open loop testing) and some steps being made on the PD (controller output).


Observations made from the closed loop section of the test
 

1. The loop was in a continuous cycle which appeared to be probably caused by bad tuning.  Although it is hard to see in the test due to the aliasing of the signals caused by a relatively slow scan rate in the OPC data interchange system which was used to pick up the signals from the DCS, this could be confirmed by running a frequency analysis on the PV signal which revealed that the period of the dominant frequency in the cycle was approximately 13 seconds.  This is typical of the frequency of cycling caused by instability due to bad tuning for a flow loop.  (As a general note such cycling generally occurs at a frequency close to the ultimate (or natural resonant) frequency of a closed loop flow control loop).

 

2. The amplitude of the cycle on the PD, was very much smaller than that of the PV (process variable) which would indicate a process gain much greater than unity.  (Process gain is the ratio of the change in PV over the change in PD).  This would indicate largely oversized valve.

 

3. This is also confirmed by the fact that the average value of the PD in the cycle was around 7%, which assuming that the  transmitter and valve calibrations were correct, would mean that the valve was working far too close to seat.  (A well established rule of thumb for most types of pneumatically operated valves is that under normal control conditions is that they should operate at or above 20% opening.  The main two reasons that valves should not work close to seat is that firstly they may encounter excessive differential pressure with which their actuators cannot cope, and secondly, the manufacturers find it very difficult to machine the valve seats and/or plugs so that the correct inherent flow characteristics can be maintained, so installed non-linear characteristics may be encountered at low flows).

 

Observations made from the open loop section of the test
 

1. The installed characteristics of the valve are non-linear which is shown by several small equal steps  in the PD being made, and the magnitude of PV increasing with each subsequent step.

 

2. The PV jumps around at times when the PD was steady which would indicate possible slight play in the linkages between actuator and actual valve.

 

3. The total change in the PV is about 10 times greater than that of the PV, which would indicate the valve is possibly about 10 times oversized., confirming the observation made above in the closed loop section of the test.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 2

 

Figure 2 shows a section of an open loop test made with a step made on the PD.  The purpose was to try and establish tuning values that could possibly work.  It is actually of interest that in this step the process gain in this case was calculated to be a massive 34!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 


 

 

 

 

 

 

 

 

Figure 3

 

A closed loop test using the new tuning is shown in Figure 3.  It is of interest that some sort of poor closed loop control was actually now being achieved.  However it again can be seen that the PV suddenly moved by itself at one point, again probably due to play in linkages.  It also showed that the PV apparently didn’t move properly on two of the SP step changes, and also apparently exhibited a lot of dead time as seen on the first large SP change downwards.  However one must be reasonable.  To get the PV to move, the PD has only to move a tiny amount and this must be done quite slowly to avoid instability.  The valve was actually doing quite a remarkable job, but it is absolutely ridiculous to try and get a good control with such a massively oversized valve.  There was no doubt that the valve needed replacing with a smaller one.


For the record the original tuning was P = 0.15, and I = 0.7 minutes per repeat, whereas the new tuning was P = 0.01, and I = 0.09 minutes per repeat.  The original P gain was 15 times too large and resulted in the instability.  Typically flow loops need tuning with a small gain and a fast integral.  The original tuning is a good example of really bad “trial and error” tuning.